21
7.0 Site Requirements
7.11 Flue Options
1. The Baxi Platinum Combi HE can be fitted with flue
systems as illustrated.
2. The standard flue is suitable only for horizontal
termination applications.
3. Maximum permissible equivalent flue lengths are:-
Horizontal Concentric 10 metres
Vertical Concentric 10 metres
Vertical Twin Pipe 15 metres
4. Any additional “in line” bends in the flue system must be
taken into consideration.
Their equivalent lengths are:-
Concentric Pipes:
45° bend 0.5 metres
93° bend 1.0 metres
Twin Flue Pipe
45° bend 0.25 metres
91.5° bend 0.50 metres
The elbow supplied with the boiler is not included in any
equivalent length calculations
5. The illustrations opposite show examples of permissible
flue systems.
6. Instructions for guidance and fitting are included in each
kit, where appropriate.
NOTE: Flue length is measured from point A to B as
shown.