27
8.0 Installation
8.9 Making The Electrical Connections
To connect the mains input cable proceed as follows:-
1. Slacken the facia panel securing screws and lift the
outercase panel so that its securing tabs are clear of the
facia. Remove the panel.
2. Completely undo the screws securing the facia panel and
hinge it down (Fig. 26).
3. Remove the control box cover securing screws.
Disengage the barbs on the control box from the cover.
Remove the cover (Fig. 27).
4. Slacken the cable clamp on the LH side of the boiler
chassis (Fig. 28). Insert the cable through the clamp and
route it to the terminal block.
5. Slacken the screws in the terminal block, connect the
input cable, and tighten the screws.
NOTE: Both the Live and Neutral connections are fused.
6. The boiler is fitted with an integral timer. If a room
thermostat is to be connected it can be done at this point.
Run the input cable from the thermostat through the second
cable clamp on the boiler chassis. Refer to the instructions
supplied with the control.
IMPORTANT: The room thermostat MUST be suitable
for 230V switching.
NOTE: An external frost thermostat cannot be used
with the integral timer.
7. Remove the link between terminals 1 & 2. The 230V
supply at terminal 1 can be connected to the thermostat.
The switched output from the thermostat must be
connected to terminal 2. (Fig. 29). If the room thermostat
being used incorporates an anticipator it MUST be wired as
shown in Fig. 29.
8. Ensure that both mains input and, where fitted, external
control input cables have sufficient slack to allow the control
box to drop down. Tighten the cable clamp(s) on the boiler
chassis.
8.10 Preliminary Electrical Checks
1. Prior to commissioning the boiler preliminary electrical
system checks should be carried out.
2. These should be performed using a suitable meter, and
include checks for Earth Continuity,
Resistance to Earth, Short Circuit and Polarity.
Commentaires sur ces manuels